Supports up to 48 Antminers or 60 Whatsminers
Up to 240kW cooling capacity to gain overclocked hashrate
Single-loop circulation
Integrates smart PDUs and networking
Integrates circulation pumps and piping
Supports either dry cooler (by default) or closed water cooling tower
High density and space saving
Easy to deploy
Supports remote management
Optional
Optional power distribution cabinet
Optional CDU module (dual loop)
Alternative closed-circuit water cooling tower
Specifications
Qty of B24 Tanks | 2 |
B24 Outer Size | 2486*746*530mm |
Input Voltage | 3-phase 350-480V 50/60Hz |
Output Voltage | Single-phase 200-277V 50/60Hz |
Cooling Capacity | 240kW@35°C |
Ambient Temp | -25°C ~ 55°C |
Net Weight (Tank) | 344kg |
Coolant Volume | 1500L |
Max Inlet/Outlet Temp | 45/65°C |
Max Power Load | 16kW |
Network | 100Mbps Ethernet switch |
Pipe Diameter | DN65 |
Dry Cooler | FHDC240 |
Dry Cooler (EC Fan) | |
Model |
FHDC240 |
Cooling Capacity | 240kW |
Circulation Medium | Oil |
Input Voltage | 3-phase 350-480V 50/60Hz |
Max Power Load (kW) | 8 |
Max Inlet/Outlet Temp (°C) | 40/45 |
Reference Temperature (°C) | 35 |
Total Air Volume (m³/h) | 56000 |
Dimensions (mm) | 2520*2200*2160 |
Noise Level @25°C, 16m | 68 |
Shipping Weight (kg) | 1110 |
Operating Pressure (MPa) | 0.3 |
Note: About the transportation of liquid cooling equipment
For most areas, the liquid cooling equipment will be shipped to you via sea freight. Ports and receiving points in different regions will incur different shipping charges. It is recommended that you contact customer service to confirm address details and calculate shipping costs before placing an order.